finale bevestiging van ondersteuning word vereis. Sodra u bestelling geplaas is, wag asseblief vir finale bevestiging van die maatskappy. ( 97144476031)
Fluke 1773 Power Quality Analyzer
0.00 AED
In stock
Product Details
UPC:
095969919012
Brand:
Fluke
Number of Inputs:
4 inputs, 3 phases and neutral referenced to PE (5 connectors)
Measurement Category:
1000 V CAT III / 600 V CAT IV
Measurement Range:
±8 kV
Bandwidth:
DC to 30 kHz for PQ measurements, excluding transients
Resolution:
24-bit synchronous sampling
Frequency:
80 kS/s at 50/60 Hz
Scaling:
1:1, variable for use of potential transformers
Sampling Rate:
1 MS/s
Dimensions:
28.0 cm x 19.0 cm x 6.2 cm (11.0 in x 7.5 in x 2.4 in)
Weight:
4.6 lbs (2.1 kg)
Memory :
8 GB internal (expandable with microSD card)
Operating Temperature:
-10 °C to 50 °C
Storage Temperature:
-20 °C to 60 °C
Interfaces:
Ethernet, USB type A, USB-C, WiFi/BLE module, LTE/4G module, GPS
Power :
Li-Ion battery BP1770 with extended temperature range, customer replaceable
1773 power quality analyser
The Fluke 1773 Power Quality Analyzer is an advanced tool designed to simplify and enhance the process of power quality logging, troubleshooting, and analysis. This three-phase power quality analyzer is ideal for professionals seeking reliable data capture and comprehensive power quality assessment.
Key Features
- High-Speed Transient Capture: The Fluke 1773 can capture transients up to 8 kV, allowing for detailed analysis of power quality events that may affect equipment performance and longevity.
- Ease of Use: With instrument powering from the measurement circuit, the 1773 eliminates the need for additional power sources, simplifying setup and usage.
- Comprehensive Data Logging: The analyzer logs voltage, current, and frequency (V/A/Hz) data, along with power parameters, dips, and swells, providing a complete picture of power quality.
- Automatic Analysis: The Fluke 1773 features automated power quality health indicators, helping users quickly identify and troubleshoot issues.
- Software Integration: The device integrates seamlessly with Fluke Energy Analyze Plus software, enabling easy download, analysis, and reporting of data for thorough evaluations.
Applications
The Fluke 1773 is perfect for a wide range of applications, including:
- Industrial Facilities: Monitor and analyze power quality to ensure machinery operates efficiently and to prevent unexpected downtime.
- Utility Companies: Assess power quality to meet regulatory requirements and ensure reliable service delivery.
- Electrical Contractors: Troubleshoot and verify power quality issues on-site to provide accurate solutions for clients.
Fluke 1773 Power Quality Analyzer Specifications
Voltage inputs | |
Number of inputs | 4 inputs, 3 phases and neutral referenced to PE (5 connectors) |
Measurement category | 1000 V CAT III / 600 V CAT IV |
Maximum input voltage | 1000 V rms / 1000 V dc (1700 Vpk) |
Nominal voltage range | Wye and single phase: variable (50 V – 1000 V) |
Delta: Variable (100 V – 1000 V) | |
IEC 61000-4-30 Class A compliance for the nominal voltages (Vdin) 100 V – 690 V | |
Input impedance | 10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE |
Bandwidth | DC to 30 kHz for PQ measurements, excluding transients |
Resolution | 24-bit synchronous sampling |
Sampling frequency | 80 kS/s at 50/60 Hz |
Scaling | 1:1, variable for use of potential transformers |
Voltage transients | |
Measurement range | ±8 kV |
Sampling rate | 1775: 1 MS/s |
1777: 1 MS/s, 20 MS/s | |
Bandwidth | DC to 1 MHz |
Trigger | Adjustable trigger level. Triggers on high-frequency components > 1.5 kHz |
Resolution | 14-bit synchronous sampling |
Current inputs | ||
Number of inputs | 4 inputs 3 phases and Neutral, range selected automatically to attached sensor | |
Range | AC | 1 A to 1500 A with i17XX-FLEX1500 12 |
1 A to 1500 A with i17XX-FLEX1500 24 | ||
3 A to 3000 A with i17XX-FLEX3000 24 | ||
6 A to 6000 A with i17XX-FLEX6000 36 | ||
40 mA to 40 A with clamp i40s-EL | ||
4 A to 400 A with clamp i400s-EL | ||
DC | 20 A to 2000 A with 80i-2010-EL clamp | |
Bandwidth | DC to 30 kHz | |
Resolution | 24-bit synchronous sampling | |
Sampling frequency | 80 kS/s at 50/60 Hz | |
Scaling | 1:1, variable | |
Input voltage | Clamp: 50 mV / 500 mV rms; CF 2.8 | |
Rogowski Coil: 15 mV / 150 mV rms at 50 Hz, 18 mV / 180 mV rms at 60 Hz; CF 4 | ||
all at nominal probe range | ||
Input impedance | 11 kΩ |
Aux inputs | |
Wired connection with 17XX-AUX adapter | |
Number of inputs | 2 |
Input range | Direct: 0 V dc to ± 10 V dc |
0 V to 1000 V dc | |
Input impedance | Direct: 2.92 MΩ |
Scale factor | Format: mx + b (gain and offset) user configurable |
Displayed units | User configurable (up to 8 characters, for example °C, psi, or m/s) |
Data acquisition voltage and current | |
Input mains frequency | DC, 50/60 Hz 15 % (42.5 Hz … 57.5 Hz, 51 Hz … 69 Hz) |
Topologies | 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye IT, 3-φ Aron/Blondel (2 element delta), 3-φ delta open leg, 3-φ high leg delta |
Data storage | Fluke 1773/1775: 8 GB internal (expandable with microSD card) |
Fluke 1777: 32 GB microSD card (installed) | |
Memory size | Typical 10 logging sessions of 8 weeks with 1-minute intervals and 100 events. |
The number of possible logging sessions and logging period depends on user requirements | |
Real time accuracy | Internal: 3 ppm (0.26 s per day, 8 s per month) |
NTP (internet time): Depending on internet latency, typical < 0.1 s absolute to UTC | |
GPS: < 1 ms absolute to UTC | |
Trend interval | |
Measured parameter | See operator manual |
Trend interval | User selectable: 1 sec, 3 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
Averaging interval min/max values | Voltage, Current: ½ cycle RMS (20 ms at 50 Hz, 16.7 ms at 60 Hz) |
Aux, Power: 200 ms | |
Total harmonic distortion | THD for voltage and current is calculated on 50 harmonics |
Power quality measurements | ||
Measured parameter | See operator manual | |
Harmonics | h0 … h50 | |
% fund and RMS for voltage, current and power | ||
Phase angles for voltage and current up to h11 | ||
Interharmonics | ih0… ih50 | |
% fund and RMS for voltage and current | ||
Supraharmonics | 2–9 kHz with 200 Hz bins | |
9–30 khz with 2 kHz bins | ||
RMS for voltage and current | ||
Harmonics measurement method | Grouped, sub-grouped and single harmonic bins according to IEC 61000-4-7. | |
Method selected automatically based on configured PQ standard or user configurable. | ||
Total harmonic distortion | Calculated on up to 50 harmonics (depends on selected PQ standard) | |
Mains signaling | 2 frequencies in the range from 110 Hz to 3000 Hz | |
Events | Voltage | Dip, swell, interruption, rapid voltage change, mains signaling, waveshape deviation, transients |
Current | Inrush current | |
Triggered recordings | Half cycle RMS of voltage and current for 10 s | |
Waveform of voltage and current for 10/12 cycles | ||
Mains signaling: 200 ms RMS of mains signaling voltage up to 120 s | ||
Transients: Waveform of voltage | ||
(Fluke 1777: 1 MS/s or 20 MS/s, 500,000 pts, Fluke 1775: 1 MS/s, 25,000 pts) |
Standard compliance | |
Power | IEEE 1459 |
Harmonics | IEC 61000-4-7: Class 1 |
IEEE 519 (short time and very short time harmonics) | |
Flicker | IEC 61000-4-15 Class F1 |
Power quality | IEC 61000-4-30 Class A, IEC 62586 PQI-A-PI |
Power quality compliance | EN 50160 + GOST + NEQUAL + NETCODE + FOL |
Interfaces | |
Ethernet | 1 Gbit/s 1000BASE-T |
USB type A | USB 2.0 high speed for USB flash drives to transfer measurement data, firmware updates and license installation. Max. supply current: 500 mA |
USB-C | USB 2.0 high speed for data download to PC and calibration (requires USB type A to USB-C or USB-C to USB-C cable) |
Auxiliary power supply for the Analyzer (requires USB C power adapter PD 2.0 or higher with 9 V 1.8 A support) | |
USB 3.0 super-speed for USB-C flash drives to transfer measurement data, firmware updates and license installation. Max. supply current: 900 mA | |
WiFi/BLE module1 | 802.11 ac 2.4 GHz / 5 GHz, support for concurrent access point and client mode |
Bluetooth 5.0/BLE | |
Antenna: Internal and external2 | |
LTE/4G module3 | LTE-A Cat 12 |
Worldwide LTE-A and UMTS/HSPA+ coverage | |
Antenna: External2 | |
GPS | MCX connector to attach a GNSS antenna for GPS/GLONASS2 |
1 Not in 177X/BASIC versions
2 Requires 5m extension cable, Fluke p/n 5263915
3 Availability and supported providers vary by country. Check with your local Fluke representative.
Parameter | Range | Resolution | Intrinsic Accuracy at Reference Conditions | |
% of Reading + % of Full Scale | ||||
Voltage | 1000 V | 0.1 V | 0.1 % of nominal voltage | |
in accordance with | ||||
IEC 61000-4-30 Class A1,2 | ||||
±(0.04 % + 0.004 %)3 | ||||
Voltage dips and swells | - | 0.1 V | 0.2 % of Vnom1,2 | |
Voltage transients | ±8 kVpk | - | ±5 % +0.25 %) | |
Voltage harmonics/interharmonics | 100% | 0.1 % / 0.1 mV | ≥1 % Vnom1: ±2.5 % of rdg. | |
<1 % Vnom1: ±0.025 Vnom | ||||
THD on voltage | 100% | 0.1 % / 0.1 V | ±(2.5 % + 0.5 %) | |
Voltage distortions 2-9 kHz | Max 100 V | 0.1 mV | ±(2.5 % + 0.1 V) | |
Voltage distortions 9-30 kHz | Max 100 V | 0.1 mV | ±(2.5 % + 0.1 V) | |
Current | With iFlex 1500 A, | 150 A | 0.01% | ±(1 % + 0.02 %) |
(Rogowski clamp mode) | i17XX-FLEX1500 24 | 1500 A | 0.1 A | |
With iFlex 3000 A, | 300 A | 0.01 A | ±(1 % + 0.03 %) | |
i17XX-FLEX3000 24 | 3000 A | 0.1 A | ||
With iFlex 6000 A, | 600 A | 0.1 A | ±(1.5 % + 0.03 %) | |
i17XX-FLEX6000 36 | 6000 A | ###### | ||
With AC clamp 40 A, | ###### | 0.001 A | ±(0.7 % + 0.02 %) | |
i40s-EL | 40 A | 0.01 A | ||
With AC clamp 400 A, | 40 A | 0.01 A | ±(2 % + 0.2 %) | |
i400s-EL | 400 A | 0.1 A | ±(0.7 % + 0.1 %) | |
With AC/DC clamp | 200 A | 0.01 A | ±(0.8 % + 0.2 %) | |
2000 A, 80i-2010s-EL | 2000 A | 0.1 A | ||
Current min/max | 100% | defined by accessory | x2 of intrinsic accuracy | |
Current harmonics/interharmonics | 100% | 0.1 % / 0.01 A | ≥3 % Inom: ±2.5 % of rdg.4 | |
<3 % Inom: ±0.15 % of Inom | ||||
THD on current | 100% | 0.10% | ±(2.5 % + 0.5 %) | |
Frequency | 42.5 Hz … 69 Hz | 0.001 Hz | ±0.01 Hz | |
Voltage unbalance | 100% | 0.10% | ±0.15 % | |
Current unbalance | 100% | 0.10% | ±0.15 % | |
Flicker Pinst, Pst, Plt | 0 to 20 | 0.01 | 5% | |
Mains signaling voltage | Up to 3 kHz | 0.1 V / 0.1 % | 1-3 % Vnom: ±0.15 % of Vnom | |
0-15 % of Vnom | 3-15 % Vnom: ±5 % of rdg. | |||
AUX input | ±10 V | 0.1 mV | ±(0.2 % + 0.05 %) | |
1 Nominal voltage in the range of 100 V to 690 V. Also known as Udin. | ||||
2 0 °C to 45 °C: Intrinsic Accuracy x2. Outside of 0 °C to 45 °C: Intrinsic Accuracy x3 | ||||
3 Only for calibration laboratories | ||||
4 With iFlex 1500A, I17XX-FLEX1500 24 |