finale bevestiging van ondersteuning word vereis. Sodra u bestelling geplaas is, wag asseblief vir finale bevestiging van die maatskappy. ( 97144476031)
Fluke 1775 Awesome Power Quality Analyzer
Fluke 1775 Awesome Power Quality Analyzer
The Fluke 1775 Power Quality Analyzer is a state-of-the-art tool designed to provide comprehensive insights into power quality. With its advanced features, this device offers a faster and more efficient way to conduct power quality studies, making it an invaluable asset for professionals in the power industry.
The Fluke 1775 Power Quality Analyzer is equipped with a wide range of features to support in-depth power quality analysis. It enables the measurement and analysis of various power parameters, including voltage, current, power, and more. The device's user-friendly interface and high-resolution display facilitate real-time data interpretation, while its robust data logging capabilities allow for detailed long-term analysis.
Fluke 1775 Awesome Power Quality Analyzer Specifications:
Voltage Inputs:
- Number of Inputs: 4 inputs, 3 phases and neutral referenced to PE (5 connectors)
- Measurement Category: 1000 V CAT III/600 V CAT IV
- Maximum Input Voltage: 1000 V rms/1000 V DC (1700 Vpk)
- Nominal Voltage Range:
- Wye and single phase: variable (50 to 1000 V)
- Delta: variable (100 to 1000 V)
- IEC 61000-4-30 Class A compliance for the nominal voltages (Vdin) 100 to 690 V
- Input Impedance: 10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE
- Bandwidth: DC to 30 kHz for PQ measurements, excluding transients
- Resolution: 24-bit synchronous sampling
- Sampling Frequency: 80 kS/second at 50/60 Hz
- Scaling: 1:1 variable for use of potential transformers
- Voltage Transients:
- Measurement Range: ±8 kV
- Sampling Rate: 1 MS/second
- Bandwidth: DC to 1 MHz
- Trigger: Adjustable trigger level, Triggers on high-frequency components >1.5 kHz
- Resolution: 14-bit synchronous sampling
Current Inputs:
- Current Inputs: 4 inputs 3 phases and neutral, range selected automatically to attached sensor
- Bandwidth: DC to 30 kHz
- Resolution: 24-bit synchronous sampling
- Sampling Frequency: 80 kS/second at 50/60 Hz
- Scaling: 1:1 variable
- Input Voltage:
- Clamp: 50 mV/500 mV rms; CF 2.8
- Rogowski coil: 15 mV/150 mV rms at 50 Hz, 18 mV/180 mV rms at 60 Hz; CF 4
- All at nominal probe range
- Input Impedance: 11 kΩ
Data Acquisition Voltage and Current:
- Input Mains Frequency: DC, 50/60 Hz ±15% (42.5 to 57.5 Hz, 51 to 69 Hz)
- Topologies: 1-φ, 1-φ IT, split phase, 3-φ delta, 3-φ wye IT, 3-φ aron/blondel (2 element delta), 3-φ delta open leg, 3-φ high leg delta
- Data Storage: 8 GB internal
- Memory Size: Typical 10 logging sessions of 8 weeks with 1-minute intervals and 100 events, The number of possible logging sessions and logging period depends on user requirements
- Real-time Accuracy:
- Internal: 3 ppm (0.26 s per day, 8 s per month)
- NTP (internet time): depending on internet latency, typical <0.1 s absolute to UTC
- GPS: <1 ms absolute to UTC
General:
- Dimensions: 11.0 x 7.5 x 2.4" (28 x 19 x 6.2 cm)
- Weight: 4.6 lbs (2.1 kg)