final confirmation from support is required. Once your order is placed, please await final confirmation from the company. (+97144476031)

Fluke 1748/15/EUS Three-Phase Power Quality Logger

0.00 AED
In stock
Product Details
UPC: 095969919012
Brand: Fluke
Number of Inputs: 4 (3 phases and neutral), mode selected automatically for attached sensor
Measurement Category: 1000 V CAT III/600 V CAT IV
Bandwidth: 42.5 Hz - 3.5 kHz
Resolution: 16-bit synchronous sampling
Frequency: 42.5 Hz to 69 Hz
Scaling: 1:1 and variable
Dimensions: 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in)
Weight: Instrument: 1 kg (2.2 lb)
Memory : Internal flash memory (not user replaceable), Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
Operating Temperature: -25 °C to +50 °C (-13 °F to 122 °F)1
Storage Temperature: Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F)
Interfaces: USB-A, Wi-Fi (free with product registration), Bluetooth, USB-mini
Power : Li-ion 3.7 V, 9.25 Wh, customer-replaceable

Fluke-1748/15/EUS Three-Phase Power Quality Logger

The Fluke-1748/15/EUS Three-Phase Power Quality Logger is an advanced tool designed for professionals dedicated to maintaining optimal power quality and system performance. It is a critical instrument in the arsenal of electrical engineers and technicians, enabling them to perform comprehensive analysis and troubleshooting of electrical systems with precision and efficiency.
What sets the Fluke-1748/15/EUS apart is its focus on user-friendliness combined with powerful data logging capabilities. The device's intuitive interface ensures that users can quickly set it up and start capturing essential data without the need for extensive training. This is particularly beneficial in fast-paced environments where time is of the essence and delays can lead to significant downtime or operational inefficiencies.
In practical terms, the Fluke-1748/15/EUS provides invaluable insights into the health and performance of electrical systems. It allows users to identify and diagnose power quality issues such as voltage dips, swells, harmonics, and other disturbances that can compromise the reliability and efficiency of electrical equipment. By capturing detailed data on these parameters, the logger helps pinpoint the root causes of problems, enabling targeted interventions that improve overall system performance and prevent future issues.
Beyond troubleshooting, this power quality logger plays a vital role in preventive maintenance and long-term system planning. Continuous monitoring and data logging help identify trends and emerging issues before they escalate into major problems. This proactive approach not only enhances the reliability of the electrical infrastructure but also contributes to significant cost savings by reducing the likelihood of unexpected failures and extending the lifespan of equipment.
The versatility of the Fluke-1748/15/EUS is further enhanced by its compatibility with various software tools that facilitate detailed analysis and reporting. This makes it easier for users to interpret data, generate comprehensive reports, and implement solutions based on accurate, real-time information. Whether for compliance with regulatory standards or for internal audits, the logger provides the necessary documentation to ensure that systems are operating within acceptable parameters.

Fluke-1748/15/EUS Three-Phase Power Quality Logger Includes:

  • Fluke 1748 Logger
  • Soft storage bag/case
  • Voltage test lead (3-phase + N)
  • Alligator clips (blue) (x2)
  • Alligator clips (black) (x4)
  • Set of cable markers
  • Mains power cable
  • Mains adapter MA-C8
  • Set of 2 test leads (stack and non-stackable, blue, 7 in.)
  • Set of 2 test leads (non-stackable, blue, 79 in.)
  • USB Cable
  • Magnet hanger kit
  • Magnet Probes (x4)
  • i17xx-flex1500IP 24 inch current probes (x4)
  • WiFi/BLE-to-USB Adapter

Fluke-1748/15/EUS Three-Phase Power Quality Logger Specifications

Parameter Range Maximum Resolution Intrinsic Accuracy at Reference Conditions (% of Reading +% of Range)
Voltage 1000 V 0.1 V ±0.1 % of nominal voltage 1, 2
Current: Direct input i17xx-flex 1500IP 24 1500 A 150 A 0.01 A (min. 1.5A)3 ±(1% + 0.02%)
1500 A 0.1 A
i17xx-flex 3000IP 24 3000 A 300 A 0.01 A (min. 3.0 A)3 ±(1% + 0.03%)
3000 A 0.1 A
i17xx-flex 6000IP 36 6000 A 600 A 0.01 A (min. 6.0 A)3 ±(1.5% + 0.03%)
6000 A 0.1 A
i40s-EL clamp ###### 1 mA ±(0.7% + 0.02%)
40 A 10 mA
Frequency 42.5 Hz to 69 Hz 0.01 Hz ±(0.1%)2
Auxiliary input ±10 V dc 0.1 mV ±(0.2% + 0.02%)
Voltage min/max 1000 V 0.1 V ±0.2 % of nominal input voltage1
Current min/max Defined by accessory Defined by accessory ±(5% + 0.2%)
THD on voltage 1000% 0.10% ± 2.5%
THD on current 1000% 0.10% ± 2.5%
Voltage harmonics 2nd to 50th 1000 V 0.1 V ≥ 1 V: ±5% of reading
< 1 V: ±0.05V
Current harmonics 2nd to 50th Defined by accessory Defined by accessory ≥ 3% of current range: ±5% of reading
< 3% of current range: ±0.15% of range
Flicker PLT, PST 0 to 20 0.01 5%
Current probe accuracy
Parameter Influence quantity iFlex1500IP-24 iFlex3000IP-24 iFlex6000IP-36 i40S-EL
150 A / 1500 A 300 A / 3000 A 600 A / 6000 A 4 A / 40 A
Active Power P PF ≥ 0.99 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Active Energy Ea
Apparent power S 0 ≤ PF ≤ 1 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Apparent Energy Eap
Reactive power Q 0 ≤ PF ≤ 1 2.5% of measured apparent power
Reactive Energy Er
Power Factor PF - ±0.025
Displacement Power
Factor DPF/cosΦ
Additional uncertainty in% of range VP-N>250 V 0.02% 0.02% 0.02% 0.02%
1 In the range of 100 V … 500 V; also known as Udin
2 0 °C … 45 °C: Intrinsic accuracy x 2, outside of 0 °C … 45 °C: Intrinsic accuracy x 3
3 Consult operators manual for details
Reference conditions:
Environmental: 23 °C ± 5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 %
Input conditions: Cosφ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 %.
Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V
Input current: I > 10 % of I range
Primary conductor of clamps or Rogowski coil in center position
Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
Electrical Specifications
Power Supply
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7)
Power consumption Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
Efficiency ≥ 68.2% (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ±15%
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtime Typically 4 hours
Charging time < 6 hours
Data Acquisition
Resolution 16-bit synchronous sampling
Sampling frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies)
Data storage Internal flash memory (not user replaceable)
Memory size Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
Basic Interval
Measured parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms)
Demand Interval (Energy Meter Mode)
Measured parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power Quality Measurements
Measured parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation
Averaging interval 10 min for all parameters
2 hrs (long term Flicker PLT)
150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
Individual harmonics 2nd to 50th harmonic
Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
Interharmonics 1st to the 50th interharmonic
Total harmonic distortion Calculated on 50 voltage harmonics
Events Voltage: dips, swells, interruptions, current: inrush current
1748: mains signaling, transients (low frequency)
Triggered recordings RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30)
Waveform of voltage and current up to 200 ms, 10/12 cycles
Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s
Inrush RMS profile based on 1/2 cycle RMS steady state triggering
Flicker In accordance with IEC 61000-4-15 and IEEE 1453
Mains signaling Two user defined frequencies up to 3 kHz
PQ Health Summarizes power quality measurements in one table. Detailed data available for each parameter
EN 50160 Compliance with standard
Programmable PQ limits Enables user defined limits for local standards compliance
Standards Compliance
Harmonics IEC 61000-4-7: Class 1
IEEE 519 (short time and very short time harmonics)
Power quality IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
Power IEEE 1459
Power quality compliance EN 50160
Safety General: IEC 61010-1: Pollution Degree 2
Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V
Power Supply: Overvoltage Category IV, Pollution Degree 2
Li-ion Battery: IEC 62133
Interfaces
USB-A File transfer via USB flash drive, firmware updates, max. supply current: 120 mA
Wi-Fi (free with product registration) File transfer and remote control via direct connection or Wi-Fi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or Wi-Fi/BLE adapter, check for availability)
USB-mini Data download device to PC
Voltage Inputs
Number of inputs 4 (3 phases referenced to neutral)
Maximum input voltage 1000 Vrms, CF 1.7
Input impedance 10 MΩ
Bandwidth 42.5 Hz to 3.5 kHz
Scaling 1:1 and variable
Measurement category 1000 V CAT III/600 V CAT IV
Current Inputs
Number of inputs 4 (3 phases and neutral), mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range
Range 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Auxiliary Inputs
Number of inputs 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
Input range 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s
Scale factor Format: mx + b (gain and offset) user configurable
Displayed units User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Bluetooth connection (check for availability)
Number of inputs 2
Supported modules Fluke Connect® 3000 series
Acquisition 1 reading/s
Environmental Specifications
Operating temperature -25 °C to +50 °C (-13 °F to 122 °F)1
Storage temperature Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F)
Operating humidity IEC 60721-3-3: 3K6:
-25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 %
40 °C (104 °F): 55 %
50 °C (122 °F): 35 %
Operating altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000 m
Enclosure IEC 60529: IP50
IEC 60529: IP65 with IP65 rated voltage connector
Vibration IEC 60721-3-3 / 3M2
Electromagnetic compatibility (EMC) EN 61326-1: Industrial CISPR 11: Group 1, Class A
IEC 61000-6-5 Power station environment
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
General Specifications
Warranty Two-years (battery not included)
Accessories: one-year
Calibration cycle: two-years
Dimensions 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in)
Weight Instrument: 1 kg (2.2 lb)
Tamper protection Accept securing cables (max. Φ 6mm)
1Warm up the product to -10 °C (+14 °F) before you power the unit on
i17XX-FLEX1.5KIP Flexible Current Probe Specifications
Measuring range 1 to 150 A ac/10 to 1500 A ac
Probe cable length 610 mm (24 in)
Probe cable diameter 7.5 mm (0.3 in)
Weight 170 g (0.38 lb)
Minimum bending radius 38 mm (1.5 in)
Nondestructive current 100 kA (50/60 Hz)
Temperature coefficient over 0.05 % of reading/°C (0.028 % of reading/°F)
operating temperature range
Working voltage 1000 V CAT III, 600 V CAT IV
Output cable length 2.0 m (6.5 ft)
Probe cable material TPR
Weight 115 g
Probe cable material TPR
Coupling material POM + ABS/PC
Output cable TPR/PVC
Operating temperature -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating -40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating 15% to 85% non-condensing
IP rating IEC 60529: IP65
Warranty One-year
Save this product for later
Share this product with your friends
Fluke 1748/15/EUS Three-Phase Power Quality Logger