finale bevestiging van ondersteuning word vereis. Sodra u bestelling geplaas is, wag asseblief vir finale bevestiging van die maatskappy. ( 97144476031)
Megger MTO250 50 A Transformer Ohmmeter
Megger MTO250
The Megger MTO250 50 A transformer ohmmeter is a field-portable, line-operated device specifically designed to safely and accurately measure the resistance of various types of magnetic windings. It is suitable for testing transformers, shunt reactors, and rotating machine windings, as well as performing low resistance measurements on connections, contacts, and control circuits.
The MTO250 is valuable for testing the winding and contact resistance of load tap changers (LTCs), as well as evaluating the 'make-or-break' transition event. Being the only moving part of a transformer, LTCs are mechanical devices and thus one of the most vulnerable components, leading to more failures and outages than any other part. Consequently, LTCs require frequent testing and maintenance to ensure safe and reliable operation.
Megger MTO250 Key Features
- Capable of testing transformers up to 1000 MVA
- DC test current up to 50 A maximum
- Integrated demagnetisation feature
- Computer control and internal data storage
- Validates proper operation of on-load tap changers
- Protected against accidental current lead disconnection (through potential leads)
Megger MTO250 Specifications
SPECIFICATION | DETAILS |
---|---|
Input | 85-264 VAC, 47-63 Hz, 1500 VA |
Output Current Ranges | 1 A / 10 A / 25 A / 50 A |
Open Circuit Voltage | 50 V DC |
Resistance and Current Measurement/Display | |
50 A | 10 µΩ to 0.04 Ω, Resolution: 0.0000001 Ω |
0.04 Ω to 0.4 Ω, Resolution: 0.00001 Ω | |
25 A | 10 µΩ to 0.08 Ω, Resolution: 0.0000001 Ω |
0.08 Ω to 0.8 Ω, Resolution: 0.00001 Ω | |
10 A | 10 µΩ to 0.2 Ω, Resolution: 0.000001 Ω |
0.2 Ω to 2 Ω, Resolution: 0.0001 Ω | |
1 A | 100 µΩ to 2 Ω, Resolution: 0.00001 Ω |
2 Ω to 20 Ω, Resolution: 0.001 Ω | |
Accuracy and Resolution | Typical Accuracy: ±0.1%, Guaranteed Accuracy: ±0.25% |
Current Resolution and Accuracy | 4 digits, ±0.25% |
Computer Interface | Via Ethernet port |
Internal Data Storage | 9 groups, 99 results per group |
LTC Make-Break Transition Settings | 2 ms, 20 ms, 50 ms, 80 ms |
Safety/EMC/Vibration | Conforms to EN61010-1, ISTA 1A, EN61326 |
Environmental | Operating: -10°C to 50°C, Storage: -25°C to 70°C, Humidity: 0-90% RH |
Dimensions and Weight | 8.5 x 21.5 x 13 inches, Unit: 30 lb, Optional leads: 29 lb, In case: 96 lb |